GDWG-III SF6 Gas Leakage Detector

GDWG-III SF6 Gas Leakage Detector

Brief Description:

GDWG-III SF6 gas leakage detector, with non-dispersed infrared (NDIR) technology, is mainly used to pinpoint and measure SF6 leakage on GIS and refilling equipment within power industry. 

 


Product Detail

Product Tags

Product Description

GDWG-III SF6 gas leakage detector, with non-dispersed infrared (NDIR) technology, is mainly used to pinpoint and measure SF6 leakage on GIS and refilling equipment within power industry.

The annual leakage rate of SF6 gas electrical equipment is measured with bandaging method. At the same time, the equipment is widely used in power supply bureau, substations, high voltage switch company, laboratory hood and scientific test.

Application

High voltage switchgear
Helicopter rotor blades
Gas transmission system
Fire extinguisher
Ventilation rate study
Hazardous material
Tank

Advantages

No radioactive risk.
No need to replace high purity argon gas regularly.
No need to replace sensor regularly, cost-effective.
No need to make linear calibration every year, no wearing parts.
Not effected by humidity, environment pollution or data drift.
When there is severe leakage or SF6 gas concentration is up to 100%, it will not be polluted or damaged.

Features

To measure SF6 gas leakage qualitatively and quantitatively. Sensitivity to SF6 gas 3g/year.
To locate SF6 gas leakage point.
Parameters like SF6 gas concentration, temperature, humidity, power indicator, date and diaphragm pump status are displayed.
User-friendly interface.
Use NDIR technology and advanced sensor from Germany.
Fast test speed and good repeatability, data is stabilized within 10s.
With temperature and pressure compensation.
No false alarm, no gas except SF6 responses.
Non-contact gas measurement ensures that sensor won’t be poisoned at any concentration rate.
Thermostatic chamber ensures no temperature drift at ambient temperature for sensor.
3.5inch OLED display, legible in the strong sunlight.
Built-in lithium battery, standby time is long.
Pipelines is customized as per request.
Pump suction sampling ensure good sealing of gas path under test.
More than 100 groups of test data are stored based on gas concentration and test time, easy to query.
The outer casing is high strength, fully shielded, ultra-lightweight ABS material structure.

Specifications

Measuring principle: Non-dispersive infrared sensor (NDIR)
Measuring range: 0-2000ppmv SF6
Resolution: 0.1ppmv
Accuracy: ±2%FS 
Even the measuring range is over 5000ppm, the instrument will not be damaged.
Repeatability error: ≤±1%
Sensitivity: 1ppmv
Response time: ≤10s
Recovery time: ≤15s
Stability: ≤±20ppm, more than 1000hours
Sampling mode: pump suction type, flow up to 1L/min.
Zero shift: ≤±1%(F.S/year)
Linear error: ≤±1%
Peak current: <700mA
Average power: <2W.
Operation air pressure: 800-1150hPa.
Environment humidity: 0-95%RH
Storage temperature: -20~+60℃
Operation temperature: -20~+50℃
Operation humidity: 0-95%(non-condensing)
Working voltage: 220VAC±10%,50Hz Or Built-in Li-battery, continuous working 6hours after full charge.
Dimension: 220×250×120mm
Weight: about 2kg

Accessories
Main unit 1 set
Charger 1 piece
Hand-held probe 1 piece
Anti-slip belt 1 piece
Hose 600mm 1 piece
Users guide 1 copy
Warranty card 1 copy

  • Previous:
  • Next:

  • Send your message to us:

    Write your message here and send it to us
    TOP